Air-conditioning compressor how there is a low-pressure pipe condensation going on, but also compressors feel cooler? Ask is a lack of fluoride do?

Category: Home Appliances Home Appliances

Question:
air-conditioning compressor how there is a low-pressure pipe condensation going on, but also compressors feel cooler? Ask is a lack of fluoride do?

Answer:
air conditioner low pressure pipe condensation, it should not due to lack of refrigerant.
is a normal phenomenon.
If it is frost, that is, lack of refrigerant in
1: In the cooling run time to see whether the outdoor unit of the connecting pipe frosting (frosting mostly refrigerant leak)
2: In the cooling run time to see water dripping from pipes, drip and whether the rate is very slow or simply does not drip. (More than an hour after the boot does not drip or dripping slowly, mostly refrigerant leak)
3: In the cooling run time with the clamp-type table check whether the current marked on nameplate rated current. (Up to less than a rated current may be refrigerant leak)
a high-level refrigeration mechanic’s answer