Question on installing air-conditioning power supply
Category: Home Appliances Home Appliances
Question:
I have two air conditioners to be installed, one for 23 a 26, the house is an old house, installed a one table, the table The rated current of 10A, do not know if small is not small?
also install air-conditioning power supply cable, the line must use four square do? Love asked, said there are 12A and 16A of the socket? How much do I need sockets, how identify the socket type呀?
Thank you for the!
Answer:
normal operating current is 23 air-conditioned 3.5A, 26 of the operating current is 4A, if the two work simultaneously together with other household appliances of the current, rated current of 10A meter is that some too much, but as long as no more than three times the rated current meter there will be no problem.
As for the outlet you have to buy two 16A, so that air conditioning is running in the socket will not be exposed to objectionable materials while heating damaged by fire. You do not identify the socket type, as long as the purchase of air-conditioned private three-hole 16A ceramic sockets on the list.
air-conditioning power cable if it is copper, then for each …